 characteristics
 of high reliability
·double conversion on-line topology structure design, make UPS output for frequency tracking, phase-locked, voltage regulator and filter the noise, not affected by power fluctuation interference of pure sine wave power, so that the UPS for the user device to provide more comprehensive and perfect protection.
·output zero transition time, meet the sophisticated equipment to power a high standard.
·modular design and dual CPU control, the reliable operation, high stability, guarantee the safe operation of the whole efficiency of UPS.
 reliability
Pure online static bypass technique, provides strong overload and fault protection device.
Built-in manual repair bypass, to further improve the reliability of continuous running load.
Environmental adaptability
UPS of the AC input voltage range up to 380V ( or 400V )±20 ﹪, thereby reducing the battery usage frequency, greatlyprolongs the service life of the cell.
UPS input frequency range, to ensure access to various fuel generator can work stably.
 of high
The intelligent battery management function ( ABM ) technology, thereby prolonging the service life of the battery, reduce the number of battery maintenance.
Advanced automatic conversion of constant current and constant voltage charging technology, the maximum activationcell, save the charging time, prolongs the service life of the cell.
 protection
With a boot from the diagnosis function, avoid pitfalls and UPS may trigger failure risk.
With the AC input over / under voltage protection; output overload, short circuit protection; inverter over-temperature protection, battery undervoltage warning / protection, battery charging protection and comprehensive protection function,greatly ensure the system stability and reliability.
·strong overload capacity, in the 110%/125%/150% overload can maintain 300 minutes /10 minutes / 1 minutes.
 capability
·insert and machine module ( optional) can achieve up to 6 units and machine, increases the reliability of the system. The system is scalable, easy to realize and machine.
And UPS can share the same set of backup battery.
·fixed master-slave relationship and the machine: in several parallel UPS, wherein the first boot the a (Master ) UPS, the other mainly from (Slave) UPS, UPS master-slave interchangeable, if a UPS inverter fault occurs, the UPS automatically output, the load from the remaining UPS to provide power supply.
 management of human nature
LCD display panel, to the user to accurately display the working condition and the working data UPS.
Through RS232 interface with UPS intelligent monitoring software and computer communications, UPS variousparameters displayed on the communication interface of stick out a mile.
·external SNMP adapter, UPS remote network management functions, to provide real-time UPS data and power supply information, through a variety of network management system for communication and management.
 
Product technical parameters



Model
FX33160 FX33200 FX33250 FX33300 FX33400
Rated capacity (W )
160K
VA
200K
VA
250K
VA
300K
VA
400K
VA
Rated capacity (W )
128KW 160KW 200KW 240KW 320KW
Rated voltage
380Vac(or 400Vac)
input
Input voltage range
380Vac(or 400Vac)±20%  Three phase four line input  
Input frequency range
50/60Hz±5Hz  Automatic identification
Power factor
>0.97             
Maximum inputcurrent
245A 310A 385A 470A 625A
oupput
Output voltage
380Vac(or 400Vac)±1%
Output frequency
Input frequency automatic tracking
Frequency stability ( battery mode )
50Hz±0.05%
Output waveform
Sine wave
Waveform distortion
Linear load < 3% < 8% nonlinear load
Power factor
0.8
Peak factor
3∶1 (max)
Overload capacity
In the 110%/125%/150% overload can maintain 300 minutes /10 minutes /1 minutes
Conversion time
 
Cityelectric modefor battery
0ms
Bypass
Rated voltage
380Vac(or 400Vac)                   
Voltage range
380Vac ( or 400Vac ) + 20% ( 10%15%20% adjustable )
Rated frequency
50/60Hz ( automatic identification )
Frequency range
±2%(±1% to  ±5%adjustable)   
Battery
 )
480
Panel display
LED
The instruction input, inverter, bypass, battery status
LCD
Display input and output voltage, frequency, battery voltage, load percentage, the temperature in the machine
Communications
Communicationinterface
Dry contact RS232 communication interface to the FX33O interface
Work environment
Operating temperature
0~40℃
Relative humidity
0~95% no condensation
Storage temperature
-25℃~55℃
Noise
< 70dB
Physical characteristics
Net weight(Kg)
1300 1350 2200 2200 2600
Gross weight(Kg)
1400 1450 2450 2450 2900
size(W× D × H)mm 1420×745×1810 1630×850×1900 1630×1000×1900
Option and machine module, harmonic filter, input isolation transformer, intelligent monitoring software,SNMP adapter
Safety standard EN50091-1 EN50091-2 Class A
YD/T1095-2000 implementation of standards

Copyright © 2004-2011 Socemen.com All Rights Reserved 京ICP备13000001号
电话:010-69734985、69739480、80767833 传真:010-80767833 Email:chendan517@126.com
地址:北京市海淀区科学院南路新科祥园9号楼21层