Product configuration characteristics
Wide input voltage range
The use of efficient filtering synchronous circuit, fast tracking synchronous frequency and power grew function, reduce the generator capacity requirements, only UPS input power 1.25 times.
Superior intelligent charging management
160-275V wide input range, allows the UPS input voltage changes in the face of huge can operate normally, and also reduces the chance of battery discharge, combined with superior charger for charging the battery, prolonging the service life of the cell.
Kindly man-machine interface
This record, can display UPS history include: battery discharge number, the number of UPS overload, inverter running time and graph display UPS instant data and state
The power input, the battery is normal
The UPS output voltage value
The output, the input frequency display
The voltage input value
The power output.
Excellent compatibility with generator
Improved UPS the weakest link, according to the battery parameter curve always provides an accurate charging current,not only can quickly replenish battery discharge energy consumption and in the end to float ( Floationg Charge ) way to charge the battery, to supplement the self-discharge of the battery energy loss, improve the efficiency of the battery.
High intelligent monitoring software
FX11 series UPS in the design of RS232 communication port, providing UPS and PC connected between thecommunication, but also in PC has powerful monitoring software.
Can do:
The power status analysis
The normal switching system of UPS
The watch UPS instant state
The implementation of UPS self diagnostic test
The automatic storage file
Support Chinese and English
▲can use the company's SNMP Adapter remote monitoring
Product technical parameter
FX11-1K ~ 20K ( single inlet and outlet type ) |
Model |
FX11-1K |
FX11-2K |
FX11-3K |
FX11-6K |
FX11-10K |
FX11-15K |
FX11-20K |
Capacity ( KW ) |
1KVA/0.8 |
2KVA/1.6 |
3KVA/2.4 |
6KVA/4.8 |
10KVA/8 |
15KVA/12 |
20KVA/16 |
Input voltage |
Single phase two wire and ground wire,220V±25% |
Battery voltage |
48V |
192V |
Noise |
≤52dB(Distance1m) |
≤60dB(Distance距离1m) |
Size
(W×D×Hmm) |
530×200×608 |
650×230×58 |
620×343×916 |
Weight ( Kg )
( not including the battery ) |
50 |
65 |
75 |
62 |
100 |
240 |
280 |
Input |
Frequency |
50Hz/60Hz±10% |
Power factor |
≥95% |
Output |
Voltage |
220V±0.5% |
Voltage adjustment |
Dynamic regulator± 1%,±2% ( <20ms, 0-100% load changes ) |
Frequency stability |
50Hz/60Hz±0.5%(Battery supply) |
The frequency of reversal rate |
Less than 1Hz/ seconds |
Instantaneous load |
( 100%± 0.4% transient load changes ) |
Harmonic distortion |
Linear load is less than 3% (full load ),
less than 5% of total harmonic rectifier |
Overload capacity |
150% |
Waveform |
Sine wave |
Efficiency |
Input AC to AC output |
More than 95% |
Conversion time |
City electric loss of d
eposit or restoration |
0 seconds |
UPS Turn to BYPASS |
Less than 4 milliseconds |
Battery |
Type |
Sealed lead-acid maintenance-free |
Charging time |
8 hours after full charge charge to 90% |
Warning sound |
Charging time |
The main power failure, tweet once every 4 seconds |
Battery low, called once per second. |
Battery discharge stop, continuous tweet |
Failure exception |
Continuous tweet |
Internal protection device LCD panel |
Battery |
Battery low energy automatic shutdown, no fuse switch protection |
Overload |
Overload ( 110~150% ) automatically after 30 seconds to j
ump to the BYPASS, automatic recovery |
Over temperature |
UPS internal temperature >85 ℃, automatically jump to BYPASS |
Output short circuit |
Current limiting, automatic shutdown, without fuse switch protection |
UPS anomaly |
Automatically jump to the BYPASS by the city power supply |
Noise filter |
10~10KHz at 40 db;100KHz~100MHz at 70db |
LCD display screen |
Display input, output voltage, frequency, battery voltage, output power ( % ) |
Battery BVL |
1 LED, battery low voltage will be bright |
Exterior environment |
Temperature |
-10~50℃ |
Relative humidity |
0%~93% ( non dewing. ) |
Operating condition |
Distance of 3000 meters below sea level |
|
|