characteristics
protection performance
The standard can be reached IP21 protection grade (to prevent more than 12mm solid objects invasion, to prevent the vertical water drop invasive). In order to better dustproof, optional dust-proof component, improve industrial environmentuser dustproof grade, ensure the UPS equipment in the harsh environment of safe operation.
)
Machines built and machine function, does not need to increase the external attachments, can achieve maximum 8 UPS parallel, is convenient for users to carry out low cost system expansion. The advanced control strategies, and redundancyin working condition.
battery charging and discharging
Advanced intelligent charging through the CPU control, UPS charger can according to different environmental conditions,correction of charging parameters, to provide optimal battery charging method.
function
According to the actual status of electricity using two electric input or a commercial power input, the user's power supply to be more security.
processor
Full digital Ti high performance DSP control technology, the data processing is accurate and quick, output performance will be more excellent, more improve reliability.
Excellent electrical performance
High efficiency up to 93%; to provide ECO mode, so that the efficiency can reach above 98%, the lower the UPS powerloss. In response to China's power grid design requirements, provides a wide range of input voltage 210VAC~475VAC.Can be applied to severe power grid environment. Excellent input frequency range UPS can adapt to different power supply device of generator. IGBT FM intelligent rectifier inverter technology, high input power factor up to 0.99, the input current harmonics of low to 3%; output voltage and current of more excellent performance.
Product technical parameters
model |
HT3320K |
HT3330K |
HT33 40K |
HT33 60K |
HT3380K |
Rated capacity
|
16KW |
24KW |
32KW |
48KW |
64KW |
input |
Voltage
|
210—475VAC |
Frequency
|
40 - 70Hz ( 50Hz and 60Hz adaptive )
|
Phase line
|
Four phase three wire and ground wire
|
THDI |
3% |
Input power factor
|
>0.99 |
Dual input
|
Support
|
output |
valtage |
220×(1±1%)VAC |
frequency |
50/60Hz |
phase line |
Four phase three wire and ground wire
|
output power factor |
0.8 |
Overload capacity
|
125% 10min |
Efficiency
|
City electricalmodel
|
93% |
Battery mode
|
93% |
ECO mode
|
98% |
Smart fan
|
Yes
|
Battery
|
Maintenance free battery
|
Voltage
|
384V |
display |
LCD |
Voltage, current, frequency, battery voltage, fault display, fault, warning
|
LED |
UPS running state
|
Warning device
|
BUZZER sound and lights flashing dual display
|
Communication interface
|
RS232, AS400, RS485, EPO. battery temperature compensation interface, intelligent slot
|
Operating environment
|
Temperature of 0-40 ℃and humidity≤ 93% [ ( 40± 2 )℃, no condensation )
|
weight(Kg) |
Net weight
|
82 |
110 |
114 |
282 |
306 |
Gross weight
|
122Kg |
160Kg |
164Kg |
356 |
380 |
size(mm) |
420×643×956 |
470×710×1150 |
800x600x1850 |
|